Energy efficiency measures - Industrial - Heat recovery - Brewery

Template assignment

Base Case
  • Wort from the kettle is cooled in a two-section heat exchanger
  • Water is preheated in section 1 and is further heated in the hot water tank
  • Heating load for hot water production is 500 kW, duty cycle of 100% and operation 2,880 h/yr
  • Refrigeration load is 1,000 kW, duty cycle of 100% and operation
    2,880 h/yr
  • Natural gas fired steam boiler seasonal efficiency is 80%
  • Refrigeration system seasonal coefficient of performance (seasonal) is 3
  • Natural gas rate is $10/GJ, electricity rate is $0.06/kWh

Proposed case
  • large temperature difference between the two stream flows in each sections of the cooler is an opportunity to further improve heat recovery
  • Increase heat transfer surface area of section 1 to recover more heat from the wort:
    • Hot stream: 18 L/s, 2,880 h/yr, 19ºC (representing the additional energy savings)
    • Cold stream: 18 L/s, 2,880 h/yr, 10ºC
    • Heat recovery efficiency is 45%
  • Increasing the heat exchanger size will increase the amount of heat recovered and therefore decrease the heating load, it will also reduce the cooling load since the wort enters section 2 at lower temperature
  • Cost of retrofit is $130,000

Base case

Base case
Proposed case

Proposed case
Solution

The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.