Cooling - Compressor - Commercial building
Template assignment
Base case
The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.
Template assignment
Base case
- 2,500 m2 building with 100 kW reciprocating compressor chiller
- Chiller has a seasonal coefficient of performance of 3.5
- Cooling load for building is 40 W/m2
- Electricity rate is $0.085/kWh
- 100 kW rotary compressor chiller costing $7,000 more than the base case system
- Chiller has a seasonal coefficient of performance of 5.0
- Maintenance requirements are lower than in base case by $300/year
- Capacity charges (demand charges) are lower than in the base case by $100/year
The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.