Cooling - Absorption - Clinic

Template assignment

Base case
  • Cooled floor area is 10,000 m2
  • Cooling load for building is 40 W/m2
  • Compressor capacity of 400 kW
  • Non-weather dependant cooling is 5%
  • Compressor-based chillers
  • Seasonal COP of 4.8
  • Electricity operates compressor and costs $0.10/kWh and $10/kW/year for peak demand charge
  • Natural gas-fired boilers provide heat during heating season
  • Building uninterruptible power supply (UPS) must have sufficient capacity to operate chillers during power outages
  • Installed cost of compressor capacity: $80,000
  • Installed cost of natural gas heating capacity: $20,000
  • Installed cost of additional uninterruptible power supply (UPS) generator capacity: $40,000

Proposed case
  • Direct-fired, double effect absorption chillers
  • Seasonal COP of 1.2
  • Chiller can also serve as natural gas-fired heater in the heating season
  • Installed cost of chiller: $160,000
  • Cost of maintaining absorption chiller/heater is around $500 less per year than cost of maintaining separate compressor and natural gas boiler units
  • Absorption chiller does not incur significant peak demand charges
  • Absorption chiller does not require significant electricity during power outages
  • Natural gas rate is $8/GJ
Solution

The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.