Cooling - Absorption - Clinic
Template assignment
Base case
Proposed case
The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.
Template assignment
Base case
- Cooled floor area is 10,000 m2
- Cooling load for building is 40 W/m2
- Compressor capacity of 400 kW
- Non-weather dependant cooling is 5%
- Compressor-based chillers
- Seasonal COP of 4.8
- Electricity operates compressor and costs $0.10/kWh and $10/kW/year for peak demand charge
- Natural gas-fired boilers provide heat during heating season
- Building uninterruptible power supply (UPS) must have sufficient capacity to operate chillers during power outages
- Installed cost of compressor capacity: $80,000
- Installed cost of natural gas heating capacity: $20,000
- Installed cost of additional uninterruptible power supply (UPS) generator capacity: $40,000
Proposed case
- Direct-fired, double effect absorption chillers
- Seasonal COP of 1.2
- Chiller can also serve as natural gas-fired heater in the heating season
- Installed cost of chiller: $160,000
- Cost of maintaining absorption chiller/heater is around $500 less per year than cost of maintaining separate compressor and natural gas boiler units
- Absorption chiller does not incur significant peak demand charges
- Absorption chiller does not require significant electricity during power outages
- Natural gas rate is $8/GJ
The worked-out solution is the data file selected from within the RETScreen Project Database. The user automatically downloads the Project Database file while downloading the RETScreen software.