- Commercial building with a constant indoor temperature of 21°C
- Thermal resistance (R-value) of the walls is 1.5 m2 - °C/W
- Design airflow rate is 7,200 m3/h
- The building ventilation is operating ten hours per day, seven days per week
- Natural gas heating with 70% efficiency
- Natural gas rate is $0.40/m3
- The base case natural gas heater is supplemented by a 80 m2 unglazed, back-pass solar air heating collector that preheats the ventilation air
- The collector is mounted on a wall (slope of the collector is 90º) that faces 25º west of south
- The percentage of time that the heating ventilation system is used are as follows:
- The solar collector shading is 10% during the season of use
- Assume a 0.70 wind sheltering coefficient (this could be done by multiplying each of the wind speed values by 0.70 in the climate data section of the Start worksheet)
- The collector is black, with an absorptivity of 0.93 and performance factor of 0.70
- The collector does not increase ventilation fan energy requirements due to the buoyancy of the solar-heated air
- The incremental installed cost of the collector is around $130/m2 for this installation
- Maintenance costs are the same as in the base case
- A government incentive is applied to the installation cost of the solar collector